Hot Water Demand Calculator ♨️

Size a water heater and storage tank from the fixtures in a building, with the ASHRAE per-fixture method: peak hourly demand, recovery rate, heater power in kW and Btu/h, and tank volume.

🧮 Inputs

Electric heaters about 98%, condensing gas 90–95%, standard gas about 80%. Only 60–80% of a tank can be drawn before the outlet temperature drops.
FixtureQtyL/h each
Auto calculate enabled (no Calculate button).
Water Heater Recovery
—
—
Heater Input
—
—
Storage Tank
—
—
Possible Demand
—
—

Breakdown

The ASHRAE Per-Fixture Method

  1. Possible maximum demand = Σ (number of fixtures × hourly demand per fixture), at 60 °C (140 °F).
  2. Probable maximum demand = possible demand × demand factor for the building type. This is the heater's required recovery per hour.
  3. Storage capacity = probable demand × storage capacity factor.
  4. Tank size = storage capacity ÷ usable fraction, since only about 70% of a tank is available before the water cools.
  5. Heater input = recovery × 4.186 kJ/kg·K × temperature rise ÷ efficiency (in US units: gph × 8.33 × ΔT°F ÷ efficiency, in Btu/h).
BuildingDemand factorStorage capacity factor
Apartment house0.301.25
Hotel0.250.80
Hospital0.250.60
Office building0.302.00
School0.401.00
Gymnasium0.401.00
Private residence0.300.70
Industrial plant0.401.00

Storage vs Recovery

A large tank lets a smaller heater cover a short peak, which suits offices and schools where most hot water is used in one short period (hence the high storage factor). Hotels, hospitals and apartments use hot water more evenly through the day, so they rely more on recovery. The trade-off can be shifted: more storage with less recovery, or the reverse, as long as the first-hour delivery meets the peak.

Safe Temperatures

Store hot water at 60 °C (140 °F) or above to control Legionella, and use thermostatic mixing valves to deliver it at a safe temperature, usually about 43–49 °C (110–120 °F) at fixtures. For peak hot water flow to size pipes, use the hot WSFU in the Fixture Unit Calculator; for the expansion vessel use the Expansion Tank Calculator.

FAQ

How do you calculate hot water demand?

Multiply the number of each fixture by its hourly hot water demand from the ASHRAE table, add them up, then multiply by the building's demand factor. The result is the peak hourly demand the heater must recover.

How do you size a hot water storage tank?

Multiply the probable maximum hourly demand by the storage capacity factor for the building type, then divide by the usable fraction of the tank, typically 0.7.

How many kW to heat water?

Heating 100 litres per hour from 10 °C to 60 °C takes 100 × 4.186 × 50 ÷ 3,600 = 5.8 kW, divided by the heater efficiency.

📚 References

  • ASHRAE Handbook – HVAC Applications, Service Water Heating: hot water demand per fixture, demand factor and storage capacity factor
  • ASPE Data Book Volume 2: domestic water heating design