FM200 Calculator: FM-200, Novec 1230 & CO₂ Agent Quantity

Size a total flooding system the way a design calculation is produced: design concentration from the hazard class and NFPA 2001 safety factor, agent quantity at the minimum room temperature, altitude correction, containers filled equally — and the concentration the supplied agent reaches at the maximum temperature, checked against the NOAEL. Enter the room as length × width × height, as floor area × height, or as a known volume. CO₂ follows the NFPA 12 design tables.

NFPA 2001NFPA 12ISO 14520FM Global DS 4-9

Inputs

1

Protected enclosure

Permanent, impermeable items only (columns, beams, solid cabinets). Raised-floor and ceiling voids protected by the same system are added to the volume, not deducted.
2

Agent and hazard

Filled from the hazard class — you may raise it
3

Conditions

Agent is sized here
For the NOAEL check
Above sea level
4

Containers

From the container data sheet
Optional — often 40–50% of the maximum

FM200 Calculation Formula (NFPA 2001)

Cdesign ≥ MEC × SF   (SF = 1.2 Class A · 1.3 Class B · 1.35 Class C)
W = (V / Smin) × C / (100 − C) × ACF   ← clean agents (FM-200, Novec 1230)
S = k1 + k2 × T  (m³/kg, T in °C)
FM-200 (HFC-227ea): k1 = 0.1269, k2 = 0.0005 · Novec 1230 (FK-5-1-12): k1 = 0.0664, k2 = 0.0002741

Concentration reached by a supplied mass M at temperature T:
x = (M / ACF) × S(T) / V  →  C = 100 × x / (1 + x)

W = agent mass (kg) · V = net volume (m³) · C = concentration (%) · ACF = atmospheric correction factor

Size at the lowest expected room temperature, because colder vapour is denser and needs more agent. Then divide the result into containers: n = ⌈W / max fill⌉, every container filled equally. Because containers are filled up and to whole increments, the agent supplied is a little more than the agent required — and it is the supplied mass, at the highest expected temperature, that sets the peak concentration occupants could be exposed to.

Minimum Design Concentration by Hazard Class

AgentClass A (MEC × 1.2)Class B, n-heptane (× 1.3)Class C (Class A MEC × 1.35)NOAELLOAEL
FM-200 (HFC-227ea)7.0% (5.8 × 1.2)
listings from 6.25%
8.7% (6.7 × 1.3)7.0% (5.2 × 1.35)9.0%10.5%
Novec 1230 (FK-5-1-12)4.2% (3.5 × 1.2)5.9% (4.5 × 1.3)4.7% (3.5 × 1.35)10.0%>10.0%

Class B fuels other than heptane — alcohols especially — need their own cup-burner value; use the Custom option. Where a space holds more than one hazard class, design for the highest concentration. The UL/FM listing of the hardware you install is the final authority on design concentration.

FM-200 Flooding Factor Table (kg/m³)

W/V = (1/S) × C/(100 − C) for HFC-227ea, sea level. Multiply by net volume to get kg. Highlighted: 7% at 20 °C.

Temp (°C)S (m³/kg)6.25%7%7.5%8%8.7%9%10%10.5%
0 °C0.1269 0.52530.59310.63890.68520.75090.77940.87560.9245
10 °C0.1319 0.50540.57070.61470.65930.72240.74980.84240.8894
15 °C0.1344 0.49600.56000.60330.64700.70900.73590.82670.8729
20 °C0.1369 0.48700.54980.59230.63520.69610.72240.81160.8570
25 °C0.1394 0.47820.53990.58160.62380.68360.70950.79710.8416
30 °C0.1419 0.46980.53040.57140.61280.67150.69700.78300.8268
40 °C0.1469 0.45380.51240.55190.59190.64870.67330.75640.7986
50 °C0.1519 0.43890.49550.53380.57250.62730.65110.73150.7723

FM-200 Flooding Factor Chart

0.4 0.5 0.6 0.7 0.8 0.9 1.0 6% 6.5% 7% 7.5% 8% 8.5% 9% 9.5% 10% 10.5% Design concentration kg/m³ 0 °C 20 °C 40 °C NOAEL 9%

Lower temperature or higher concentration needs more agent. Above the 9% NOAEL, NFPA 2001 limits occupant exposure.

CO₂ Design Tables (NFPA 12)

Surface fires, 34% — net volumekg/m³Not less than
Up to 3.96 m³1.15—
3.96 – 14.15 m³1.074.5 kg
14.15 – 45.28 m³1.0115.9 kg
45.28 – 127.35 m³0.9045.4 kg
127.35 – 1,415.00 m³0.80113.5 kg
Over 1,415.00 m³0.741,135.0 kg
Deep-seated hazardDesignkg/m³
Dry electrical, spaces up to 56 m³50%1.60
Dry electrical, spaces over 56 m³ (min. 91 kg)50%1.33
Record (bulk paper) storage, ducts, covered trenches65%2.00
Fur storage vaults, dust collectors75%2.66

Small rooms get higher factors because they have more boundary — and more leakage — per cubic metre. Above 34% for surface fires, the table quantity is multiplied by the material conversion factor of NFPA 12 Figure 5.3.4 (for example about 1.67 at 50%). Openings that cannot close and ventilation that cannot shut down need additional CO₂; deep-seated hazards must reach 30% within 2 minutes and the design concentration within 7 minutes. Confirm the factors against the edition of NFPA 12 in force.

Worked Example: Server Room 6 × 5 × 3 m

  1. Net volume V = 6 × 5 × 3 = 90 m³ (no deductions). From a drawing that gives the floor area instead: 30 m² × 3 m = the same 90 m³.
  2. Class C electronic hazard, FM-200: 5.2 × 1.35 = 7.0% design concentration
  3. Minimum temperature 18 °C: S = 0.1269 + 0.0005 × 18 = 0.1359 m³/kg
  4. W = (90 / 0.1359) × 7 / 93 = 49.85 kg at sea level
  5. Site at 300 m: factor 0.96 → W = 47.86 kg
  6. Containers of 67 kg maximum: 1 container, filled to 48.0 kg
  7. Maximum temperature 27 °C: S = 0.1404; x = (48.0 / 0.96) × 0.1404 / 90 = 0.0780 → 7.24%, below the 9.0% NOAEL ✓

The same room protected with CO₂ for a dry electrical (deep-seated) hazard: 90 m³ is over 56 m³, so 1.33 kg/m³ × 90 = 119.7 kg (not less than 91 kg) — three 45 kg cylinders, in a space that must be normally unoccupied. To size the standby battery for the releasing panel, use the Fire Alarm Battery Calculator. For the wider design method, see the Fire Fighting System Design Calculation guide.

Frequently asked questions

What is the FM200 calculation formula?

NFPA 2001 gives W = (V / S) × C / (100 − C), where W is the agent mass in kg, V the net protected volume in m³, C the design concentration in % and S the specific vapour volume in m³/kg at the minimum room temperature. For HFC-227ea, S = 0.1269 + 0.0005 × T, with T in °C.

How much FM-200 is needed per cubic metre?

At 7% design concentration and 20 °C, the flooding factor is 0.550 kg/m³. A 90 m³ room therefore needs about 49.5 kg at sea level, before the agent is divided into containers.

What design concentration should I use for FM-200?

NFPA 2001 sets the minimum design concentration from the extinguishing concentration and a safety factor: 1.2 for Class A, 1.3 for Class B (n-heptane cup burner) and 1.35 for Class C. For HFC-227ea that gives about 7.0% for Class A and C and 8.7% for Class B. The system listing for your hardware is the final authority.

Why check the concentration at the maximum temperature?

Agent is sized at the minimum expected temperature, where the vapour is densest. In a warmer room the same mass occupies more volume, so the concentration rises. For a normally occupied space that higher figure is the one compared with the NOAEL — 9.0% for HFC-227ea and 10.0% for FK-5-1-12.

Is FM-200 safe for occupied spaces?

Yes, at normal design concentrations. The NOAEL of HFC-227ea is 9.0% and the LOAEL is 10.5%. Between the two, NFPA 2001 limits exposure time and requires that occupants can leave promptly; above the LOAEL it is not permitted in normally occupied spaces.

How is CO2 quantity calculated?

NFPA 12 uses flooding factors that depend on the room volume, because small rooms leak proportionally more. For surface fires at 34%, a 90 m³ room uses 0.90 kg/m³ — 81 kg — compared with about 68 kg from the theoretical equation. Deep-seated hazards use higher factors, such as 1.33 kg/m³ for dry electrical rooms over 56 m³. CO2 at these concentrations is lethal, so it is only used in normally unoccupied spaces.

Why does altitude reduce the clean agent quantity?

Air is less dense at altitude, so less agent is needed to reach the same volume concentration. NFPA 2001 gives an atmospheric correction factor — 0.96 at 300 m and 0.93 at 610 m, for example. Using the factor for the table altitude at or below the site, rather than interpolating, is the conservative choice.

Can I enter the floor area instead of length and width?

Yes. Choose "Area × Height" and enter the floor area from the drawing with the room height; the net volume is area × height minus any solid objects. If you already know the protected volume, choose "Volume" and enter it directly.

References & standards

  • NFPA 2001 - Standard on Clean Agent Fire Extinguishing Systems (total flooding quantity, minimum design concentration and safety factors, atmospheric correction, exposure limits)
  • NFPA 12 - Standard on Carbon Dioxide Extinguishing Systems (Table 5.3.3 surface-fire flooding factors, Figure 5.3.4 material conversion factor, Table 5.4.2.1 deep-seated hazards)
  • ISO 14520 - Gaseous fire-extinguishing systems
  • FM Global Data Sheet 4-9 - Clean Agent Fire Extinguishing Systems

Comments

0 comments

Found a number that looks wrong, or a case the tool does not cover? Say so here — corrections are welcome and get answered.

No comments yet. Be the first to add one.

Leave a comment

Every comment is read before it appears. Links and email addresses are not accepted in the comment text — describe the point in words instead. Your email address, if you give one, is used only to reply to you and is never shown on the page.