Size a diaphragm expansion tank for a closed heating or chilled water system, or for thermal expansion of a water heater, with the ASHRAE formula.
v1, v2 are the specific volumes of water at the fill and maximum temperatures, α the linear expansion of the piping, and P1, P2 the absolute fill and maximum pressures at the tank. Water expands about 3.0% from 10 °C to 82 °C; steel piping takes up about 0.25% of that. The denominator is the acceptance factor: the larger the pressure band, the smaller the tank.
Related: Hot Water Demand Calculator, Boiler Feed Pump Calculator.
Use the ASHRAE formula: tank volume = system volume × net expansion fraction ÷ (1 − P1/P2), with absolute fill and maximum pressures. For 1,500 L heated from 10 °C to 82 °C between 150 and 270 kPa gauge, about 128 L (a 140 L standard tank).
Equal to the cold fill pressure at the tank, so the diaphragm starts to move as soon as the water expands.